NHIE Sample Questions & Answers
Free National Home Inspector Examination practice questions with worked answers and explanations. See how the ExamJungle simulator prepares you — then jump into the full test.
Launch the full NHIE simulator →Showing 6 of 12 free samples.
- Question 1Intermediate
Property and Building Inspection/Site Review · Decks, Balconies, Stoops, Stairs, Steps, Porches and Associated Railings
While inspecting an exterior wood deck attached to a single-family residence, an inspector notes that the 2x8 preservative-treated ledger board is secured with 1/2-inch lag screws directly through exterior stone veneer into the house rim joist. How should the inspector report this condition?
Show answer & explanation
Correct answer: A
IRC R507.9.1.1 strictly prohibits attaching deck ledgers to or over brick or stone veneer because veneer cannot support vertical deck loads and prevents positive structural clamping.
- Question 2AdvancedSelect 2
Property and Building Inspection/Site Review · Decks, Balconies, Stoops, Stairs, Steps, Porches and Associated Railings
An inspector is evaluating guardrail and stair rail openings on an elevated exterior deck that stands 42 inches above the lawn. Which TWO of the following opening limitations comply with standard building safety provisions? (Select TWO)
flowchart TD Walking["Deck Surface Guard (>30 in)"] --> G4["Max 4 in Sphere Opening"] StairRail["Stair Guard Infill"] --> G438["Max 4-3/8 in Sphere Opening"] StairTriangle["Bottom Rail & Tread/Riser"] --> G6["Max 6 in Sphere Opening"]Show answer & explanation
Correct answers: B, D
IRC R312.1.3 mandates that intermediate rails or balusters on elevated guards cannot permit the passage of a sphere 4 inches (102 mm) in diameter.
IRC R312.1.3 exception permits the triangular opening formed by the bottom rail, tread, and riser to be sized such that a 6-inch (152 mm) sphere cannot pass.
- Question 3Advanced
Property and Building Inspection/Site Review · Decks, Balconies, Stoops, Stairs, Steps, Porches and Associated Railings
An inspector is evaluating a second-story exterior wood deck that extends 12 feet out from the main building framing. The deck ledger is constructed of 2x10 preservative-treated lumber fastened to a 1-inch engineered rim board.
Upon checking underneath the deck assembly, the inspector observes that the ledger is attached to the house using 3-inch spiral framing nails driven straight into the rim board, with no lag screws or through-bolts present. Additionally, there are no lateral hold-down tension hardware devices connecting the deck joists to the interior floor framing.
Which of the following describes the primary structural hazard and correct reporting action for this deck assembly?
Show answer & explanation
Correct answer: A
Deck ledgers relying on nails in withdrawal fail catastrophically under load. IRC requires 1/2" bolts or lag screws and approved hold-down tension ties resisting lateral loads.
- Question 4Intermediate
Property and Building Inspection/Site Review · Floor Structure
In a residential crawlspace, an inspector examines 2x10 solid-sawn floor joists (nominal depth 9.25 inches) spanning 14 feet. A subcontractor has cut a rectangular notch measuring 2 inches deep by 4 inches long into the bottom edge of a joist in the outer one-third of the span. According to standard wood framing provisions, how should this notch be evaluated?
graph LR A[End 1: D/4 notch max] --- B[Outer 1/3 Span: D/6 notch max] --- C[Center 1/3 Span: No Edge Notches] --- D[Outer 1/3 Span: D/6 notch max] --- E[End 2: D/4 notch max]Show answer & explanation
Correct answer: C
Per IRC R502.8.1, edge notches cannot exceed D/6 (9.25 / 6 = 1.54 inches) and are prohibited in the middle third. A 2-inch notch exceeds this limit and weakens the joist.
- Question 5Beginner
Property and Building Inspection/Site Review · Floor Structure
In solid-sawn lumber floor framing, bored holes drilled for electrical cabling or plumbing lines must maintain a minimum clear distance of _____ from the top edge, bottom edge, or any other hole or notch.
Show answer & explanation
Correct answer: B
IRC R502.8.1 requires bored holes in solid-sawn joists to be no larger than D/3 and located not less than 2 inches from top or bottom edges, notches, or other holes.
- Question 6Intermediate
Property and Building Inspection/Site Review · Floor Structure
During a basement inspection, an inspector observes engineered wood I-joists supporting the ground floor. A plumber has cut a 1.5-inch notch out of the bottom wood flange of an I-joist to accommodate a copper water distribution pipe. What is the inspector's proper determination?
Show answer & explanation
Correct answer: A
Per IRC R502.8.2, cuts, notches, and holes in engineered I-joist flanges are prohibited. Flanges carry extreme tension/compression; severing them compromises structural integrity.
Ready for the real thing?
The full NHIE simulator has every exam-style question, timed mode, and instant scoring.